Answers about transformer oil testing, 11kV switchgear servicing, protection relays, generators, thermal scanning, cable location and dry ice blasting from our Cape Town medium voltage specialists.

Our FAQs are grouped into eight categories to make it easier for you to find your answers

Transformer Maintenance & Oil Testing

Transformer oil provides both electrical insulation and cooling. Oil testing can identify moisture, contamination, dielectric deterioration and signs of internal faults. Tests such as breakdown voltage, moisture content, acidity, dissolved gas analysis (DGA) and furan testing can help determine the transformer’s condition to establish what corrective maintenance is required to prolong the equipment’s life expectancy.

The maintenance frequency depends on the transformer’s age, loading, environment, manufacturer recommendations, criticality and operating history. Routine visual inspections should be performed regularly, while oil analysis should be scheduled annually according to the site’s maintenance programme. Older or critical transformers may require more frequent condition monitoring.

The transformer is visually inspected annually for oil leaks, damaged or cracked bushings, rust, abnormal noise or vibration, loose connections, damaged cables, oil level, breather condition and temperature indicators.

Secondly, the transformer oil is sampled and placed in a sealed tin. The oil is then tested by a SABS & SANAS accredited laboratory. Results typically take 2 weeks. Once we have the oil results back, we make further recommendations for corrective maintenance based on the visual inspection and oil results.

We use a purification plant with a heat-vacuum system. The purification process restores the insulating properties of transformer oil by removing moisture, dissolved gases and solid contaminants from the oil. Under normal circumstances the process can be done without power isolation and typically takes 2–3 hours.

How the process works

  1. Oil is circulated from the transformer through the purification plant.
  2. Heating raises the oil to a controlled temperature, reducing its viscosity and helping release dissolved moisture and gases.
  3. The heated oil enters a vacuum chamber, where reduced pressure causes moisture and dissolved gases to separate from the oil at a lower temperature.
  4. Filtration removes suspended particles and other contaminants from the oil.
  5. The purified oil is returned to the transformer, and the process is repeated until the required oil condition is achieved.

Note that purification does not remove acidity or improve the interfacial tension. Should the lab results fail acidity or interfacial tension, the transformer will require an oil change.

Transformer oil regeneration is a more intensive treatment process than standard oil purification. The process is lengthy and takes more than 24 hours. It is used to restore the properties of aged and degraded transformer oil by removing not only moisture and particles, but also dissolved acidic compounds, oxidation products, sludge and other polar contaminants that have accumulated over time.

During regeneration, the oil is circulated through a treatment system containing a special adsorbent material. The adsorbent captures the degradation products and contaminants from the oil. The treated oil is then filtered. The regeneration plant is large and not practical to move.

In simple terms: purification cleans the oil, while regeneration restores degraded oil by removing the chemical products of ageing and restoring the oil’s insulating properties. The Regeneration plant is large and not practical to move. The process is lengthy and takes more than 24 hours.

11kV Switchgear, Protection & Switching

The frequency of 11kV switchgear maintenance depends on the switchgear type, operating environment and criticality of the installation. However, we recommend that all 11kV switchgear be inspected and tested annually as part of a preventative maintenance programme.

Annual preventative maintenance allows developing faults and deterioration to be identified at an early stage, including insulation deterioration, mechanical defects, loose connections, oil or gas-related issues and protection-system faults. Early identification of these conditions can help prevent costly equipment failures, unplanned outages and potential safety incidents.

For oil-insulated switchgear, the condition of the insulating oil can deteriorate over time due to contamination, moisture ingress and ageing. Deteriorated oil can result in reduced dielectric strength, increasing the risk of insulation breakdown, internal arcing or flashover.

Maintenance may include visual inspection, cleaning, checking connections and wiring, verifying relay settings, testing protection functions, secondary injection testing, checking trip circuits and confirming that the circuit breaker responds correctly to a relay trip command.

A faulty relay may fail to trip during a fault or may trip unnecessarily. Either condition can create significant safety risks and potentially result in extensive damage to transformers, switchgear, cables or other electrical equipment. Faults should therefore be investigated and rectified before the protection system is returned to service.

Switching is the controlled process of isolating, de-energising, proving dead and safely earthing 11kV electrical equipment before maintenance can begin. It involves following an approved switching procedure to ensure that the correct equipment is isolated and cannot be accidentally re-energised while work is in progress.

11kV switching must only be performed by authorised and appropriately trained personnel. Personnel responsible for switching should have the required ORHV (Operational Rules for High Voltage) training and certification/authorisation applicable to the installation and network.

Because switching medium voltage equipment can present an arc-flash and electrical hazard, the person performing the switching must wear the specified arc-rated/fire-resistant switching suit and appropriate PPE required by the site’s electrical safety procedures and risk assessment. Switching is a critical safety function and must be carried out strictly in accordance with the approved switching programme, site procedures, manufacturer’s requirements and applicable electrical safety regulations.

Yes, the generator can operate during an 11kV switchgear or transformer maintenance shutdown. The 11kV supply is temporarily isolated and the required switching, isolation and lockout procedures are implemented to ensure the maintenance area remains safely de-energised.

Power Factor Correction

Power factor correction improves the electrical efficiency of an installation by reducing the amount of reactive power drawn from the electrical supply. Capacitor banks are commonly installed to compensate for inductive loads such as transformers, motors and pumps, improving the power factor and reducing unnecessary current flow through the electrical network.

Maintaining a good power factor can reduce electrical losses, improve available system capacity and minimise demand-related costs or power factor penalties, where applicable. Correctly designed PFC equipment also helps optimise the performance of the electrical installation and reduces the loading on cables, transformers and switchgear.

Older plastic-moulded PFC capacitors can present an increased fire risk as they age and deteriorate. Prolonged exposure to electrical and thermal stress can cause the capacitor dielectric and internal components to degrade, potentially resulting in overheating, internal failure, arcing or rupture.

Modern PFC capacitors incorporate improved self-healing dielectric technology and internal safety protection, such as pressure-sensitive disconnection, which helps limit the risk of catastrophic failure. For this reason, aged or deteriorated plastic-moulded capacitors should be assessed and replaced where necessary to maintain the safety and reliability of the power factor correction system.

Standby Generators

Generator servicing should be carried out in accordance with the manufacturer’s recommended maintenance intervals and operating hours. Regular servicing typically includes engine oil and filter replacement, fuel and air filter inspection, battery checks, coolant inspection and testing of the generator’s electrical and protection systems. Additional inspections may be required for generators operating under frequent starts, high loads or harsh environmental conditions.

A standby generator that remains unused for extended periods can develop fuel system problems, battery deterioration, lubricant degradation and mechanical or electrical faults. Regular starting, inspection and testing under an appropriate load helps ensure the generator remains operational and ready for use during a mains power failure.

Thermal Scanning & Infrared Inspections

Thermal scanning, or infrared thermography, is a non-invasive inspection method used to identify abnormal temperature patterns in electrical equipment. It can detect overheating connections, loose or high-resistance joints, overloaded circuits, unbalanced loads and developing component faults without physical contact with the energised equipment.

Thermal scanning helps identify potential faults before they result in equipment failure, unplanned outages or fire. Early detection of abnormal heat allows corrective maintenance to be planned before a minor connection or component problem develops into a major failure.

Yes. Thermal imaging can identify abnormal temperature patterns on motors, VSDs, terminals, cable connections and associated electrical equipment. Hotspots can indicate issues such as overloaded circuits, poor connections, cooling problems or component deterioration.

No. Thermal scanning is normally performed while the electrical equipment is energised and under load, allowing abnormal temperature conditions to be identified under actual operating conditions. The inspection can typically be carried out without interrupting the power supply.

Cable Location & Cable Faults

Cable location is the process of identifying and tracing the position and route of underground electrical cables before excavation, maintenance or repair work. Specialist cable locating equipment is used to trace the cable route and, where applicable, determine its approximate depth to help prevent accidental cable damage, service interruptions and safety incidents.

Cable faults can result from ageing insulation, mechanical damage, moisture ingress, overheating, incorrect installation, joint or termination failure, excavation damage or electrical stress. Identifying the underlying cause is important to prevent the fault from recurring.

Cable location helps identify underground electrical services before excavation or civil work begins. Correctly locating cables reduces the risk of striking an energised cable, which can result in electric shock, arc flash, equipment damage, power outages and costly repairs. It is an important precaution before any excavation in areas where underground services may be present.

Dry Ice Blasting

Yes. Dry ice blasting can be used for cleaning electrical substations, transformers, generators, switchgear and industrial electrical equipment, subject to a suitable risk assessment and equipment-specific requirements. Because the dry ice sublimates on impact, it leaves no water or abrasive blasting residue, making it particularly useful for applications where water or conventional abrasive cleaning is unsuitable.

Dry ice blasting provides waterless, non-abrasive cleaning with minimal secondary waste. It can remove contamination from complex components and hard-to-reach areas while reducing the need for dismantling and manual cleaning. The process is suitable for removing oil, grease, carbon, dust and other industrial contaminants, helping restore equipment cleanliness while minimising surface damage.

Motors & Variable Speed Drives

Motor and drive services can include inspection, testing, fault finding, maintenance, repairs and commissioning of electric motors, variable speed drives (VSDs), starters and associated control equipment.

A VSD controls the speed and torque of an electric motor by adjusting the frequency and voltage supplied to the motor. This allows equipment to operate more efficiently and provides greater control over processes such as pumps, fans and conveyors.